ENGLISH       中文版

Vacuum Circuit Breaker

Current location:Home > Product center > Vacuum Circuit Breaker
ZW7-40.5 outdoor high voltage vacuum circuit breaker
  Detailed introduction

1.Product Introduction

ZW7-40.5 series outdoor high voltage  AC vacuum circuit breaker is 3 phase AC 50Hz outdoor high voltage switchgear; Equips the CT19BW type spring operating device spring actuator,applies to control and protect of 35kv power transmission and distribution system;This product has the advantages of the big breaking capacity,safe and reliable operation,frequent operation,lowmaintenance and so on;Also could be used in the places of the network interconnecting circuit breaker,open/close capacitor bank.

The circuit breaker accords with the standard of the GB1984-2003(AC high voltage circuit breaker) and IEC62271-100: 2001(AC high voltage circuit breaker).

2.Use condition

2.1.Altitude:Not more than 2500m;

2.2.Ambient temperature:-35℃~+40℃;

2.3.Relative humidity:monthly average not more than 90%;

daily average relative humidity not more than 95%;

2.4.Seismic intensity:not more than 8 degree;

2.5.The environment polluted tolerance values:3 degree;

2.6.Icing-thickness:20mm;

2.7.Wind speed:not more than 34m/s;

2.8.Installation site should not be inflammable,explosive,chemical corrosive substances and the place of violent vibration regularly

3.Structure and working principle

3.1.This kind of the circuit breaker’s structure is porcelain pillar type,the upper porcelain bottle is the arcing chamber porcelain,in-built vacuum arc extinguishing chamber,the under porcelain bottle is the strut porcelain column, 3 phase porcelain bottles are installated on a box structure together.Arcing chamber dynamic side contacts the output shaft of the spring mechanism through the connecting lever and the insulating tension pole.The link rod between the spring mechanism and the circuit breaker is in a waterproof mechanism boxThe product is mainly made up of the vacuum arc extinguishing  chamber,CT,transmissio me chanism and the spring operating mechanism.

3.2.Arc extinguish chamber of the circuit breaker Arc extinguish chamber is the main part of the circuit breaker.

The vacuum arc-extinguishing chamber which the circuit breaker equips has the very high vacuum degree,as the arcing chamber contact terminal is CuCr50 material,choose the  cup shape and longitudinal magnetic field structure,has the advantages of the big breaking capacity,high insulation level ,strong arcing ability,long lifetime,small volume,simple maintenance,no explosive danger,non-pollution,low noise and so on.

The vacuum arc-extinguishing chamber is installed inside of the upper porcelain bottle,not only avoid the oil rush and the drawbacks of  SF6 gas filling,but also make the overhaul and maintenance more convenient, insulation material silicon ester is filled between the arc-extinguishing chamber and the porcelain bottle,solve the problem of the prevent gel,this insulation material has the characteristic of the good insulation performance,ageing resistant,outdoor resistant and high temperature resistance.

3.3.Spring operating actuator and the connecting rod are installed inside of the mechanism box,the mechanism box is the waterproof type.To prevent the casing electrical control components damp, the mechanism box equips the temperature controller and the heater.

3.4.The transmission mechanism includes the insulating tension pole,the connecting lever and the guide rod,adjust the length of the insulating tension pole and the guide rod,could adjust the overtravel and the clearance between open contacts of the circuit breaker.

4.Arc quenching principle

When the moving contact and the fixed contact charged break brake under the effect of the  operating mechanism, will have the vacuum arc among the contact terminals.Meanwhile,because of the special structure of the contact terminal,will  produce the appropriate longitudinal  magnetic field in the contact terminal’s interval,makes the vacuum arc keep the diffuse type, and also maintains a low arc voltage.When the current natural zero,the residual ions and electrons and the metallic vapor will be compound in the time of the order of magnitude of millisecond or condensation on the contact surface  and the shield,The strength of the arcing chamber fracture dielectric insulation will be recovered very soon, then the arc is been extinguished to achieve the breaking purpose.




   The previous:ZW8-12 outdoor high voltage vacuum circuit breaker
   The next:ZW79M-40.5 outdoor permanent magnet vacuum circuit breaker
Contact us
  • Tel:+86-379-64316180
  • Fax:+86-379-64282773
  • E-mail:lycndq@hotmail.com
  • TradeManager:chinacndq
  • Skype:chinacndq
Copyright © 2015 LUOYANG CHENNUO ELECTRIC CO.,LTD. Tel: 86-0379-64316180 E-Mail: lycndq@hotmail.com